- Generator tester UIG-50/70-315 designed for testing the dielectric strength of the windings of generators, conductors by line frequency AC voltage and measurements current leakage rectified voltage according to the requirements of the "Regulations for Electrical" and RD 34.45-51.300, with a maximum power to the load up to 315 kVA.
- Supply voltage 3-phase AC (50 Hz), V : 380 ± 38
- Consumption power, kV∙A, max : 30
- Continuous operation at maximum capacity, min, max : 20
- Break after continuous use, min, min : 40
- Output power, kV∙A : 315
- Capacitance range of objects test, uF : 0,05 – 0,8
- Q-factor, min : 55
- Greatest operating voltage AC test mode stator winding, kV : 35
- Greatest operating voltage AC test mode trunking, kV : 50
- Greatest operating voltage of the rectified current-leakage test, kV : 70
- Reduced error measuring current and voltage, max, % : 3
- Threshold protection high-voltage side, A : 10
- Threshold protection low-voltage side, max, A : 80
- Dimensions L × W × H, mm : 2200×1700×1760
- Warranty life, h : 1200
- Weight, kg, max : 2900