Bộ điều khiển nhiệt độ RKC SRZ
Temperature control module (Z-TIO)
- Number of Inputs :4 points or 2 points
- Input type (Universal input within each group) ※See the Input Range Code for the input range.
1) Thermocouple: K, J, R, S, B, E, N, T, W5Re26/W26Re, PLII
2) RTD: Pt100, JPt100 (3-wire system)
3) DC voltage (Low): 0 to 10mV, 0 to 100mV, 0 to 1V
4) DC current: 0 to 20mA, 4 to 20mA
5) DC voltage (High): 0 to 5V, 1 to 5V, 0 to 10V
- Sampling time : 0.25 sec.
- Measurement accuracy : ±(0.2% of displayed value+1 digit ※Depends on the input and the range.
- Outputs 1 and 2 (OUT1, 2)
1) Relay contact output: 1a contact
2) Voltage pulse output for SSR driving: 0/12V dc
3) DC Current output: 0 to 20mA, 4 to 20mA dc
4) DC voltage output: 0 to 5V, 1 to 5V, 0 to10V
5) SSR (Triac) output : Output: Current rating: 0.5A
6) Open collector output: Sink type
- Event (alarm) function: Max.4 points ※Including LBA function
- Communication function: RS-485
- Optional functions: Output distribution function, Nice MEET function, Automatic temperature rise function, Peak current suppression function
- Master-slave function, SV selection function (Remote SV, Ratio setting, Cascade control)
<Specification of Options>
- CT input for heater break alarm (Max.4 points) ※Can be used for time proportioning output and continuous output.
General Specification
- Power supply voltage (Rating): 24V dc
- Ambient temperature: -10 to 55°C
- Weight:
Screw terminal type:Approx.160g
Connector type: Approx.140g
- Safety standards:UL UL61010-1
cUL CAN/CSA-22.2 NO.61010-1
CE Marking: Low Voltage Directive (LVD) EN61010-1
EMC Directive EN61326-1
RCM EN55011
Digital Input/Output module (Z-DIO)
- Digital inputs: ※See Input assignment table for model
Number of inputs: 0 or 8 points
Input method: Voltage contact input, Sink type
- Digital outputs: ※See Input assignment table
Number of outputs: 0 or 8 points
Output types: 1) Relay contact output, 1a contact
2) Open collector output, Sink type
- Communication function: RS-485