| Rated Primary Current |
DC/AC500A |
| Rated Secondary Current |
100mA |
| Applicable Current |
0~±800A |
| Max. Capable Current |
±800A |
| Nominal CT Ratio |
1:5000 |
| CT Inside Diameter |
φ30.2mm |
| Applicable Frequency |
0~±100kHz |
| Accuracy |
±0.6% F.S |
| Response Time |
Approx. 1μs |
| Power Supply |
±15V~±24V±5% (Bipolar) |
| Power Consumption |
24mA+Output (at±18V) |
| Output Part |
Molex 6410 |
| Wiring Method |
+:+12~+24V M:Output -:-12~-24V |
| Rated Voltage |
Less than DC/AC500V for low voltage circuit of coated wires |
| Withstanding Voltage |
AC3500V/1 minute (between output terminal and CT) |
| Insulation Resistance |
More than 100MΩ by 500V insulation tester (between output terminal and CT) |
| Operation Temperature |
-40℃~+70℃, less than 75%RH w/o condensation |
| Dimension |
70×70×31mm |
| Weight |
Approx. 230g |
| Standard |
Compliant with RoHS directive
|