Specifications
Display: LCD |
Inputs: potentiostatic sensor 3 wires
polarographic sensor 2 wires
galvanic sensor 2 wires
Pt100 |
| Polarization: -200 mV adjustable +/- 800 mV on request |
Scales: 0/1.999 - 0/19.99 - 0/199.9 - 0/1999 selectable
-10.0/120.0 °C |
| Slope: 0.4 - 4 - 40 µA of the selected scale |
| Temperature compensation: manual and automatic |
Temperature coefficient: 0/4.0 %/°C
(2%/°C for Chlorine / 2.5%/°C for Ozone) |
| Reference temperature: 20 °C |
| Zero: adjustable +/- 15% |
| Sensitivity: adjustable 86/112% (coarse 20/200%) |
| Output: 4/20 mA isolated |
| Operating temperature: 0/50°C |
| Operating humidity: 95% without condensate |
| Power: 10/30 Vdc |
| Isolation: 500 V from input to output |
| Weight: 200 g |
| Dimensions: 105 x 95 x 58 mm |
| Mounting: DIN rail (6 modules) |