Use Environment |
Ambient temperature |
-30 ° C ~ +50 ° C; |
Relative humidity |
≤95%; |
Wireless communication technical indicators |
Signal power |
≤ 10dbm; |
Signal band |
433Mhz; |
Sensitivity |
-106dBm; |
Transmission distance |
in the case of line-of-sight, reliable transmission distance of 250 meters from the ground 2 meters |
Analyzer technical indicators |
Applicable DC system voltage level |
24V (customized), 48V, 110V, 220V or user-specified voltage level |
System positive and negative voltage measurement range |
0-300V |
DC voltage measurement range to ground |
0-300V |
AC series power failure alarm threshold |
5V |
Voltage measurement resolution |
0.1V |
System ground resistance measurement range |
0—999.9KΩ |
Grounding resistance measurement resolution |
0.1KΩ |
Display mode |
LCD |
Detection signal current size |
0-2mA adjustable |
Detection signal voltage amplitude |
0-50V adjustable |
Signal frequency |
no signal mode and 0.16Hz optional |
DC-resistant system distributed capacitance interference |
1000uF |
Detector technical indicators |
Insulation resistance detection range of branch circuit in signal mode |
System voltage rating is 220V |
0 -600KΩ |
System voltage rating is 110V |
0 -300KΩ |
System voltage rating is 48V |
0 -60KΩ |
System voltage rating is 24V |
0 -20KΩ |
Insulation resistance measurement resolution |
0.1KΩ |
Insulation resistance detection range of branch circuit in no signal mode |
System voltage rating is 220V |
0 -50KΩ |
System voltage rating is 110V |
0 -25KΩ |
System voltage rating is 48V |
0 -10KΩ |
System voltage rating is 24V |
0 -5KΩ |
Insulation resistance measurement resolution |
0.1KΩ |
Waveform display time |
12 seconds |
Current measurement range |
±100mA |
Current measurement resolution |
0.01mA |
Display mode |
LCD |
Direction display mode |
same or opposite direction |
Anti-DC system branch distribution capacitance interference |
100uF |
Distance to use with the analyzer |
no distance limit |
Jaw size |
Diameter 30mm |