● Usage Environment
Input Power: 220V±10%, 50Hz±10% / GDKC-12B: 230V±10%, 60Hz±10%
Air Pressure: 86-106kpa
Temperature: -10-40℃
Humidity: ≤80%RH
● Safety Performance
Insulation Resistance>2MΩ
Dielectric Strength: Shell can withstand power frequency voltage 1.5kV at 1 minute without flashover and arcing.
● The Basic Parameters
a. Time: Range 20000.0ms resolution 0.01ms
Error 0.1ms ±1digit within 2000ms
1ms±1digit within 20000ms
GDKC-12B The Basic Parameters
a. Time: Range 20000.0ms resolution 0.01ms
Error 0.01ms ± 2digit within 250ms
0.1ms ± 2digit within 2500ms
1ms±2 digit within 20000ms
GDKC-13A Circuit Breaker Analyzer The Basic Parameters
Time: Range 4000.0+6000.0 ms resolution 0.1ms
Error 0.1ms ± 1digit within 100ms
0.1% ± 1digit more than 100ms
Same period
b. Velocity: Range 20.00m/s resolution 0.01m/s
Error ±0.1m/s±1digit within 0-2m/s
±0.2m/s±1digit above 2m/s (± 0.2m / s ± 1digit more than 100ms)