Use power |
AA alkaline batteries (R6P) 8 this |
Rated measurement voltage |
DC1000 / 5000V |
Valid maximum display value |
DC1000V range 2000Emuomega
DC5000V range 100GΩ |
Measurement range |
1000V range
first effective measurement range
2MΩ ~ 1000MΩ
second effective measuring range
1MΩ ~ 2MΩ less than
1000MΩ ~ 2000MΩ
scale of * 6MΩ red
5000V range
measurement range 0.01GΩ ~ 100GΩ
effective measurement range 0.05GΩ ~ 50GΩ
scale of * 5GΩ (5000MΩ) red |
tolerance |
1000V range
first effective measurement range ± 5% of the indicated value
± 10% of the second effective measuring range indicated value
5000V range
± 10% of the effective measurement range indicated value |
Open-circuit voltage |
Within times 1-1.1 rated measured voltage |
Indicating type |
Analog meter |
Response time |
Within 3 seconds at the center instruction and zero indication |
Discharge function |
Automatic discharge function (discharge resistance 5MΩ)
during * discharge circuit operation will light "discharge in the lamp."
* Residual charge will stop if below about 50V.
* It does not work when the measurement switching voltage switch is "OFF". |
Battery check |
Confirm the power lamp of lighting color
green about 8.4V or more, less than about 8.4V red |
usage environment |
0 ~ 40 ℃ 0 ~ 80% |
External dimensions |
225 (D) × 260 (W) × 105 (H) (excluding projections) |
Case dimensions |
300 (D) × 320 (W) × 120 (H) |
weight |
About 1kg (body only, including the battery) |
accessories |
High pressure application code (one 3m) · ground cords (3m1 pcs.) Guard code (3m 1 pcs), AA alkaline batteries (8) Operating Instructions |