Use power |
Built-in battery: Nickel-cadmium battery (DC12V 2.5Ah)
DC external power supply: DC12V
AC external power supply: AC100V ± 10% 50 / 60Hz |
Output voltage |
DC 0 ~ 11kV (negative polarity) |
voltmeter |
3 1/2 digit resolution 0.01kV |
Measurement accuracy |
10kV for ± 1% ± 1dgt |
Insulation resistance tester |
Analog indicating instrument
within 10% ± with respect to measurement accuracy indicated value |
Current recorder output |
1μA in DC10mV |
Voltage recorder output |
1kV in DC10mV |
Automatic discharge function |
To discharge the charge of the DUT in the output switch OFF. |
charging |
AC external power supply (AC100V ± 10% 50 / 60Hz) |
Memory contents |
Memory leakage current of the high-voltage output, the trigger current-time memory |
Memory measured current |
0.01μF ~ 40μA (Low range) 0.2μ ~ 800μA (Hi range) |
Measurement accuracy |
10μA for ± 3% |
Judgment items |
Current value, Narukyokuhi, kick phenomenon, weakness ratio (in the PC software) |
External dimensions |
200 (D) × 390 (W) × 220 (H) |
weight |
7kg |
accessories |
Test code set (with storage bag) owner manual high vault view software |