Power supply |
AC100V ± 15% 50 / 60Hz |
Permissible interruption time |
10msec or less (at maximum load) |
Power consumption |
15VA
report when 12VA
standby 0.6VA |
Power outage report for battery |
Ni-Cd 3.6V 600mAh
life three years (at25 ℃), however, will vary depending on usage. |
External size |
38 (D) × 130 (W) × 200 (H) |
weight |
1.5kg |
accessories |
Antenna, two ZCT |
Current transformer specifications |
ZCT hole diameter φ22mm |
Leakage current detection unit |
Monitoring the number of circuits |
4 circuit |
Measuring frequency |
50 / 60Hz |
Sensitivity current value |
50/100/200/300/ 400/500/600/700 / 800mA 9 range
switching method using a digital code switch, or, you can make any set on the screen. |
Operating accuracy |
With respect to the set current value, ± 5% or less |
Operating time |
2 seconds / (program optional) |
Return value |
And 80% ± 5% of the set current value |
Recovery time |
2 seconds (automatic) |
Report information |
Text sentence |
Report Symbol silver |
Electronic formula |
DC input |
Connect the four non-voltage contact or signal of open collector, it is possible to alarm the message during operation.
If you want to use in temperature detected in the specification of the thermistor, it can alarm in the case was continued for 90 ℃ 2 minutes. |
battery |
Ni-Cd battery 3.6V 600mA with a private connector cable
time of delivery are located in the state where the battery is discharged. Therefore, you will be able to power outage report normally from 24 hours after charging. (You can not power failure compensation within 24 hours after use) |