◆ transmission unit |
Use power |
AC100V ± 10% 50 / 60Hz |
Primary current CT |
5/10/15/20/25/30/40/50/60/75 / 80A |
Corresponding pulse |
50000 pulse composite power meter (CT pulse output type) |
Power conversion method |
Min 15 (45) of every hour, from 20 (50) minutes to 30 (60) minutes pulse count that has been accumulated in every minute until, and in terms of the respective data to the predicted value of 30 minutes. |
Power comparison method |
Each installed capacity set value 50000 pulses (maximum), to calculate the number of pulses of the alarm power setting.
Alarm power pulse number = alarm power setting ÷ installed capacity set value × 50000
Note output pulse number = alarm power pulse number × 0.8 |
Clock function |
30 minutes Measurement |
Power failure compensation |
Compensation in the lithium-ion battery |
Clock Set |
In the lamp lighting of five minutes will do the setting. |
Contact output system
(alarm, note both) |
Semiconductor contact (a contact) relay output
(AC125V, 0.5A / DC24V, 1A ) resistive load |
Contact input signal |
Send a contact state to the receiver |
The number of transmission contact |
3CH |
Transmission method |
Specified low-power (10mW) |
◆ the receiving unit |
Display content |
Current power, setting power, the display of the elapsed time |
lamp |
Warning of demand alarm, note the operation
state of the external contact (3CH)
communication abnormal state |
Alarm contact output |
External contact 3CH, alarm, note the contact
when it is impossible to communicate with the sending unit, communication fault contact |
buzzer |
Warning of demand alarm, note contact
intermittent sound during the operation
when the communication of a transmission unit is abnormal, continuous sound |