Use power |
AC100V ± 10V 50 / 60Hz |
Zero-phase voltage output (current) |
range |
AC25 / 250/500 / 1000V 25 / 250mA |
capacity |
50VA30 minute rating (25V range, 5VA)
current output maximum load impedance about 85Ω |
Indicating instrument |
Moving coil-shaped, with a 1.0 grade mirror |
Output stability |
Each range ± 1% |
Frequency stability |
± 0.1% or less |
Total distortion factor |
Less than 1% |
Overcurrent protection |
Attenuation at about 110% of the rated capacity |
Zero-phase current output |
range |
AC 0.5 / 1.5 / 5A |
capacity |
0.5A maximum load impedance 12Ω (continuous)
1.5A maximum load impedance 4Ω (continuous)
5A maximum load impedance 12Ω (Continuous)
10A maximum load impedance 0.6Ω (30 minute rating) |
Indicating instrument |
Moving coil-shaped, with a 1.0 grade mirror |
Output stability |
Each range ± 1% |
Frequency stability |
± 0.1% or less (output frequency set by the panel surface) |
Total distortion factor |
Less than 1% |
phase |
Adjustable range |
LEAD175 ° ~ 0 ~ LAG175 ° (fine adjustment range about 20 °) |
Indicating instrument |
Moving-coil type ± 3 ° with mirror |
Inertia output |
0 ~ 999ms resolution 1ms ± 1ms (zero-phase voltage, control both the zero-phase current) |
Test output |
Zero-phase voltage, the zero-crossing output (zero-phase current depends on the phase adjustment.) |
VR test |
Voltage output method |
Using the zero-phase voltage output circuit, fine adjustment knob test voltage, the coarse adjustment knob to adjust the reference voltage. |
Voltage switching time |
Switching by the toggle switch, it will switch within 1ms regardless of the switch operation. |
counter |
0 ~ 199.999sec resolution 1Ms
200 ~ 1999.99Sec resolution 10ms (with automatic carry |