Use power |
AC100V ± 10V 50 / 60Hz |
Zero-phase voltage output (current) |
range |
AC25 / 250/500 / 1000V 25 / 250mA |
capacity |
50VA30 minute rating (25V range, 5VA)
current output maximum load impedance about 85Ω |
Indicating instrument |
Moving coil-shaped, with a 1.0 grade mirror |
Output stability |
Each range ± 1% |
Frequency stability |
± 0.1% or less |
Total distortion factor |
Less than 1% |
Overcurrent protection |
Attenuation at about 110% of the rated capacity |
Zero-phase current output |
range |
AC0.5 / 1.5 / 5 / 10A |
capacity |
0.5A maximum load impedance 12Ω (continuous)
1.5A maximum load impedance 4Ω (continuous)
5A maximum load impedance 12Ω (Continuous)
10A maximum load impedance 0.6Ω (30 minute rating) |
Indicating instrument |
Moving coil-shaped, with a 1.0 grade mirror |
Output stability |
Each range ± 1% |
Frequency stability |
± 0.1% or less (output frequency set by the panel surface) |
Total distortion factor |
Less than 1% |
phase |
Adjustable range |
LEAD175 ° ~ 0 ~ LAG175 ° (fine adjustment range about 20 °) |
Indicating instrument |
Moving-coil type ± 3 ° with mirror |
Inertia output |
0 ~ 999ms resolution 1ms ± 1ms (zero-phase voltage, control both the zero-phase current) |
Test output |
Zero-phase voltage, the zero-crossing output (zero-phase current depends on the phase adjustment.) |
VR test |
Voltage output method |
Using the zero-phase voltage output circuit, fine adjustment knob test voltage, the coarse adjustment knob to adjust the reference voltage. |
Voltage switching time |
Switching by the toggle switch, it will switch within 1ms regardless of the switch operation. |
counter |
0 ~ 199.999sec resolution 1Ms
200 ~ 1999.99Sec resolution 10ms (with automatic carry function) |
Counter accuracy |
0.01 Pasento rdg ± ± ± 1Dgt 5Ms ± ⊿T
⊿T: each error of the stop signal
contacts, DC voltage 1Ms ±
AC voltage (5 ~ 10V) ± 5Ms
AC voltage (10 ~ 20V) ± 2.5Ms
AC voltage (more than 20V) ± 1ms
self-power ± 3ms
case of ※ stop due to self-supply, depends on the supply load state of the power supply (back electromotive force due to the rotation device, etc., the residual voltage of the capacitor, etc.).The above accuracy, power supply of the counter is the accuracy of to completely cut off. |
Stop signal |
Contact: a contact, b contact automatic detection
voltage: direct current, alternating current with 10 ~ 220V applied, remove
the self-power: there is no power at the same time tester and the display time for about 5 minutes (the relay is operated, it is that the counter is stopped. )
* with automatic reset function |
Auxiliary power |
AC100V, DC24V, DC48V, DC110V
(AC100V is 500VA · DC output is 30W) |
External dimensions |
370 (D) × 585 (W) × 240 (H) |
weight |
21kg |
accessories |
Test code set (with storage bag) owner manual case cover |