Use power |
AC100V ± 10% 50 / 60Hz |
Power capacity |
Up to about 1000VA below 40A at the output |
Output current |
Output range |
AC0 ~ 40A (40A 15 seconds rating) |
range |
AC0.1 / 0.25 / 0.5 / 1 / 2.5 / 5/10/25 / 50A |
Maximum load impedance |
0.1A range: 4Ω 0.25A range: 2Omu
0.5A range: 1Ω 1A range: 0.5Omu
2.5A range: 0.8Ω 5A range: 1Omu
10A range: 0.5Ω 25A range: 0.8Omu
50A range: 0.5Ω (40A at the output) |
ammeter |
0.1 / 0.25 / 0.5 / 1 / 2.5 / 5/10/25 / 50A
1.0-class effective value in terms of method of moving coil-shaped average value |
Output voltage |
Output range |
AC0 ~ 1000V |
Output capacity |
40VA |
range |
AC30 / 150/300/500 / 1000V |
voltmeter |
AC30 / 150/300/500 / 1000V
1.0 grade moving coil type True RMS conversion method |
Trip current |
Short circuit 10A output open circuit voltage 100V |
counter |
Measurement range |
0 ~ 199.999sec resolution 1Ms
200.00 ~ 1999.99Sec resolution 10ms (automatic borrow) |
contact |
a contact, b contact automatic detection |
Voltage |
DC, AC both 10 ~ 220V applied, removed |
Self-powered |
Relay is there is no power at the same time tester and operated, about 5 minutes counter stop display time |
OCR alone |
Current argument detects the current change of the type of circuit breaker disconnect |
Auxiliary power |
AC100V (outputs the input power) 5A |
External dimensions |
270 (D) × 440 (W) × 220 (H) |
weight |
About 16kg |
accessories |
Test code set (with storage bag) manual case cover |