Use power |
AC100V ± 10% 50 / 60Hz |
AC voltage measurement |
Highest measured voltage |
AC30.00kV |
Measurement frequency range |
40Hz ~ 1kHz (sine wave) |
Input resistance |
100MΩ ± 1% |
Display resolution |
0.01kV |
Measurement accuracy |
± 0.5% rdg ± 10dgt ※ frequency 45 ~ 65Hz measured voltage 1kV or more |
AC current measurement |
Output current |
AC50 / 100/200 / 500mA / 1 / 2A |
Maximum load impedance |
It depends on the configuration of the current output circuit switch |
Series resistance |
Large 500Ω (50mA), 200Ω (100mA), 100Ω (200mA), 20Ω (500mA), 10Ω (1A), 5Ω (2A) |
Series resistance |
Small 2000Ω (50mA), 500Ω (100mA), 200Ω (200mA), 40Ω (500mA), 10Ω (1A), 5Ω (2A) |
Display resolution |
0.01 / 0.01 / 0.01 / 0.1mA / 0.0001 / 0.0001A |
Measurement accuracy |
± 0.5% rdg ± 10dgt (each range of 10% or more) |
DC voltage measurement |
Highest measured voltage |
DC60.00kV |
Input resistance |
6GΩ ± 1% |
Display resolution |
0.01kV |
Measurement accuracy |
± 0.5% rdg ± 10dgt ※ measured voltage 1kV or more |
DC current measurement |
Output current |
DC20 / 200μA / 2mA |
Maximum load impedance |
30kΩ (20 / 200μA), 15kΩ (2mA) |
Display resolution |
0.001 / 0.01μA / 0.0001mA |
Measurement accuracy |
± 0.5% rdg ± 10dgt |
Accuracy guarantee conditions |
Standard temperature 23 ℃ from the standard use state JISZ8703, standard humidity 65% |
Use temperature and humidity range |
5 ~ 40 ℃ 20 ~ 80% RH |
External dimensions |
Detecting section 100 (D) × 100 (W) × 650 (H) measurement unit and detecting portion housing 415 (D) × 740 (W) × 310 (H) |
weight |
About 28kg during the detection portion housing |
accessories |
Detector - measuring unit over code, ground cord, power cord, current output code, detecting unit fixing bracket |