- Built-in battery system in the 0 ~ 40kV to output , extra-high voltage for the pressure test, it can insulation diagnostic test , power supply, built-in battery, external AC100V, is 3 power system of external DC12V.
- The power supply unit, integrated measurement unit, lightweight design in the compact. And pressure testing of the vacuum circuit breaker (valve pressure test) is possible
Thông số kỹ thuật
Use power |
Built-in power supply DC12V
external power supply DC12V
power capacity 15A or more (that the power of the output terminal is not grounded)
external power supply and charging AC100V (50 / 60Hz) |
Internal battery |
Lead-acid battery (DC12V 4.5Ah 1 pcs) |
Power consumption |
Up to 400W |
Output voltage meter |
DC40kV 1.0 grade with mirror |
Output ammeter |
10Myuei / 100Myuei / 1MA / 10MA / SHORT
5-stage switching 1.0 grade with mirror |
Current Symbol green meter output |
1μA in DC10mV |
Output accuracy |
Within ± 2% ※ that the input impedance of the recorder is 1MΩ or more |
Voltage recorder output |
1kV in DC10mV |
Output accuracy |
Within ± 5% ※ that the input impedance of the recorder is 1MΩ or more |
Output voltage |
DC0 ~ 40kV (negative polarity) step variable voltage 6/12/18/24 / 36kV |
Output current |
2.5mA (short-circuit), 1mA (when -40k occurs) |
Ripple |
Within ± 1% of the output voltage value (-1 ~ -40kV) |
Load variation rate |
Within ± 1% for the FS -40kV (connecting the rated load than the no-load) |
External dimensions |
390 (D) × 250 (W) × 320 (H) |
weight |
About 17.5kg |
accessories |
Test code set (with storage bag) and discharging resistance bar owner manual case cover |