Measuring range 1) GUS–53_–01–_
GUS–53_–02–_
GUS–53_–06–_
GUS–53_–10–_
GUS–53_–20–_ |
0.1 ... 1 m
0.2 ... 2 m
0.2 ... 6 m
0.4 ... 10 m
0.5 ... 20 m |
Supply voltage GUS–53N–_ _–_ |
18 ... 36 V DC |
Current supply GUS–53N–_ _ –_–P
GUS–53N–_ _ –_–S |
max. 12 mA
disconnected 4 mA / connected 20 mA |
Current output GUS–53N–_ _ –_–P
Voltage output GUS–53_–_ _ –_–S
|
PNP transistor with an open collector
(max. switch current 300 mA)
two-state current switch 4 mA / 20 mA |
Resolution |
< 1 mm |
Accuracy GUS–53_–01 in area 0.1–0.2 m / 0.2–1.0 m
(within the total range) GUS–53_–02; –06
GUS–53_–10; –20 |
0.3 % / 0.2 %
0.15 %
0.2 % |
Temperature error |
max. 0.04 % / K |
Beamwidth (-3 dB) GUS–53_–01–_ ; 02–_ ; 10–_
GUS–53_–06–_
GUS–53_–20–_ |
10°
14°
12° |
Ambient temperature range GUS–53_–01–_ ; 02–_ ; 06–_
GUS–53_–10–_ ; 20–_ |
-30 ... +70 °C
-30 ... +60 °C |
Measuring period GUS–53_–01–_ ; 02–_
GUS–53_–06–_
GUS–53_–10–_
GUS–53_–20–_ |
0.6 s
1.0 s
1.8 s
5.0 s |
Averaging |
4 measurement |
Short time temperature stress resistance |
+90 °C / 1 h. |
Max. operation overpressure (on transmission surface) |
0.1 MPa |
Failure indication echo failure – basic mode
echo failure – inverse mode
level in dead zone – basic mode
level in dead zone – inverse mode |
3.75 mA / 0 V
22 mA / 10.5 V
22 mA / 10.5 V
3.75 mA / 0 V |
Protection class |
IP 67 |
Recommended cable |
PVC 2 x 0.75 mm2 (3 x 0.5 mm2) |
Maximal current output load resistance atU = 24 V DC
at U = 22 V DC
at U = 20 V DC |
Rmax = 270 Ω
Rmax =180 Ω
Rmax = 90 Ω |
Delay between supply GUS–53_–01–_ ; 02–_ ; 06–_
power rise time and first GUS–53_–10–_; 20–_
measurement
|
5 s
9 s |
Process connection GUS–53_–01–_
GUS–53_–02–_
GUS–53_–06–_
GUS–53_–10–_
GUS–53_–20–_ |
thread G ¾‘‘
thread G 1‘‘
thread G 1½‘‘
thread G 2¼‘‘
aluminium alloy flange |
Weight GUS–53_–01–_
GUS–53_–02–_
GUS–53_–06–_
GUS–53_–10–_
GUS–53_–20–_ |
0.20 kg
0.20 kg
0.25 kg
0.65 kg
2.80 kg |